Users set of parameters ( Please refer to the Chinese version of that ) | |||||||
ID | Function | Code | Default value | SMS Format | Parameters | Description | SMS Reply |
1 | Telephone number set up | HM | 1234*HM*139xxxxxxxx* 139xxxxxxxx* 130xxxxxxxx* 1060577xxxxxxxx# |
Set 1 ~4 phone numbers, Each number up to 16 digits |
Up to four telephone numbers, After the number of new, The original number by the new numbers in place of |
Connect the alarm telephone numbers | |
2 | Change Password | MM | 1234 | 1234*MM*8888*8888# | 4 digits or letters | old password:1234 new password: 8888 |
One Device password:8888 |
3 | Edit device name | DH | Transformer | 1234*DH*One Device# | 1~8 Chinese characters | One device name is "One device" | One Device |
4 | Temperature alarm set value | WBT | 80 105 |
8888*WB*75*WT*100# | 000~125 | Over-temperature alarm set for 75 ℃ temperature Tripping temperature of 100 ℃ |
One device Alarm temperature 75 ℃, Trip temperature 100 ℃ |
5 | Value of current alarm settings | LBGL | 200 150 |
8888*LB*1000*GL*800# | Current ratio:0000~2000 Alarm value:0000~2000 |
Current transformer current ratio of 1000:5; Alarm set value is 800A |
One device 1000:5 current ratio, current 800A |
6 | Alarm set value voltage | DYGY | 165 264 |
8888*DY*165*GY*264# | 000~500 | Low-voltage alarm set value is 165V, Alarm value of high-voltage 264V |
One low-voltage equipment, 165V, High Voltage 264V |
7 | Automatic security time interval | FG | 4 | 8888*FG*4# | 0~9 | Set up a garrison to restore security after the automatic time interval | 4h interval automatic security |
8 | Inspection interval | SJ | 24 | 8888*SJ*48# | 00~99 | Set time intervals for inspection within 48 hours | Inspection interval 48h |
9 | The contents of the standby interface alarm | J1 | 8888*J1*Open the door* J3*Note# |
1~8 Chinese characters | Such as: doors on the 1st detection port switch; Gas port on the 3rd relay (Each no more than the contents of eight Chinese characters) |
J1 One equipment cabinet doors open, J3 gas relay |
|
10 | Alarm from a defended position | CF | 8888*CF# | A state of alarm from the monitor, there is alarm Also send text messages without warning |
One device has been moved away | ||
11 | Security alarm | SF | 8888*SF# | To enter a state of alarm monitoring | Inspection SMS | ||
12 | Query status | ZT | 8888*ZT# | Query the status of equipment, real-time work | Inspection SMS | ||
13 | Remote tripping | TZ | 8888*TZ# | Remote control device tripping | One device remote control tripping | ||
14 | Remote switch | HZ | 8888*HZ# | Switch on the remote control equipment | One device remote control switch | ||
Note: 5 corresponds to the number of back-up interface.。 Set alarm values for each parameter can be sent to "#" is the end, but up to a maximum of more than 65 characters, all uppercase letters. Parameter set to "0", this feature off. Such as equipment used for the first time when the code set up, temperature, current, voltage alarm value: 1234 * DH * One device * WB * 80 * WT * 120 * LB * 200 * LC * 150 * DY * 165 * GY * 264 #, At this point I set the device code-named equipment, alarm temperature: 80 ℃; tripping temperature: 120 ℃; transformer current ratio: 200:5; current overload alarm: 150A; low-voltage alarm: 165V; high-voltage alarm: 264V. Set message to send, no reply alarm, check whether or not to send the correct message format and re-sent. |